10A DOUBLE GPO POWER POINT WITH IN-BUILT RCD

Code: 8226335   
    The Double GPO with integrated RCD automatically deactivates outlets upon detecting a fault in connected equipment, providing optimal protection for devices in workshops or garages. It features a 30mA rated trip current and complies with AU/NZ safety standards. **Product Code: PS4048** **Warranty:** 1 Year **Power Supply:** 240V Mains Power This unit serves as a direct replacement for standard GPO fittings, offering two 240AC 10A mains outlets with built-in RCD for enhanced electrical shock protection. In case of appliance faults or accidents, such as cutting through the mains lead, it ensures complete isolation from the mains. The unit includes a test button, status indicator, and reset button for RCD verification, recommended before each use. **Compliance:** Meets Australian and New Zealand safety standards. **Installation:** Must be performed by a licensed electrician. **Key Features:** - Electric shock protection - LED status indicator - Reset and test buttons - Line power indicator **Technical Specifications:** - RCD Classification: Type II - Rated Tripping Current: 30mA - Operating Speed: <40mS Max. - L/Nin-L/Nout: 2KV - Endurance: 2000 Cycles Minute - Contact Break: Double Pole - Standards: RCD Module-AS NZS 3190, Socket-AS NZS 3112 - Minimum Back Box Depth: 35mm - Fixing Screws: M3.0 x 25mm - Cable Capacity: 4x2.5mm², 2x4mm², 1x6mm129